In-Row Liquid-to-Liquid CDU
The In-Row Liquid-to-Liquid CDU integrates control, pump power, buffering, and heat exchange functions into a single unit. Through a circulation pump, the coolant with constant pressure and flow rate is continuously delivered to the supply-side pipeline and evenly distributed to server cabinets via the looped piping network. After absorbing heat from server nodes, the cooling medium flows back through the return-side pipeline and exchanges heat with the primary-side coolant through the CDU heat exchange module. The heat is then transferred to the external environment. The cooled medium returns to the circulation pump, is pressurized, and re-enters the supply-side loop, forming a closed-loop cooling system.
PRODUCT FEATURES:
◆ Cooling capacity range: 300–2300 kW, suitable for large-scale data center.
◆ Redundant safety design for key components, supporting online maintenance.
◆ N+1 redundancy for pumps, control sensors, and secondary-side filters.
◆ Dual power inputs, optional ATS support.
◆ Three control modes: differential pressure, constant flow, and constant temperature.
◆ SUS304 stainless steel piping, high reliability and coolant compatibility.
◆ Compatible with both top and bottom piping on primary and secondary sides.
◆ Integrated real-time water quality monitoring (pH, conductivity, turbidity)
◆ 7’’ LCD touch screen with PLC controller and integrated monitoring of temperature, flow, pressure, leakage, and liquid level.
◆ Supports Modbus RTU, Modbus TCP/IP, and SNMP protocols.
◆ Three-level alarm mechanism for rapid fault diagnosis.
BEEHE IN ROW L2L CDU TECHNICAL PARAMETERS:
|
Product Mode |
IB300 |
IB600 |
IB1350/IB1350P |
IB1800 |
IB2300 |
OCP Deschutes IB2000 |
|
Rated Cooling Capacity |
300kW |
600kW |
1350kW |
1800kW |
2300kW |
2000KW |
|
Cooling Medium |
PG25 |
PG25 |
PG25 |
PG25 |
PG25 |
PG25 |
|
Approach Temperature |
5℃ |
5℃ |
4℃ |
4℃ |
4℃ |
3℃ |
|
Primary-Side Inlet/Outlet Temp. |
35℃/46℃ |
35℃/43.2℃ |
35℃/47.5℃ |
35℃/45.2℃ |
35℃/45.2℃ |
37℃/52.9℃ |
|
Secondary-Side Supply/Return Temp. |
40℃/51℃ |
40℃/50.1℃ |
39℃/53℃ |
39℃/50.3℃ |
39℃/50.3℃ |
40℃/55.9℃ |
|
Secondary-Side Rated Flow Rate |
445LPM |
900LPM |
1440LPM/1800LPM |
2400LPM |
3450LPM |
1893LPM |
|
Flow Rate Range |
10-100% |
10-100% |
10-100% |
10-100% |
30-100% |
40-100% |
|
Available External Head |
21.7PSI |
36PSI |
36PSI |
42PSI |
42PSI |
80PSI |
|
Power Supply Input |
3P AC380V 50/60Hz 3P AC480V 60Hz |
3P AC380V 50/60Hz 3P AC480V 60Hz |
3P AC380V 50/60Hz 3P AC480V 60Hz |
3P AC380V50/60Hz 3P AC480V 60Hz |
3P AC380V50/60Hz 3P AC480V 60Hz |
3P AC380-480V 50/60Hz
|
|
Maximum Power Consumption |
≤5.5kW |
≤12.2kW |
≤19kW / ≤25kW |
≤32.8kW |
≤40kW |
≤74kW |
|
ATS |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
|
Pump Configuration |
1+1 |
1+1 |
1+1 |
1+1 |
1+1 |
1+1 |
|
Secondary-Side Filter |
100μm |
50μm |
50μm |
50μm |
25μm |
25μm(Side stream is 0.2μm@3GPM) |
|
Primary-Side Filter |
500μm |
500μm |
500μm |
500μm |
500μm |
500μm |
|
Communication Protocol |
Modbus RTU&TCP/ IP&SNMP |
Modbus RTU&TCP/ IP&SNMP |
Modbus RTU&TCP/ IP&SNMP |
Modbus RTU&TCP/ IP&SNMP |
Modbus RTU&TCP/ IP&SNMP |
Modbus RTU&TCP/ IP&SNMP |
|
Group Control Function |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
|
Liquid Quality Monitoring Function |
Yes |
Yes |
Yes |
Yes |
Yes |
No |
|
Automatic Refill Function |
Yes |
Yes |
Yes |
Yes |
Yes |
No |
|
Net Weight |
1297Ibs |
1763.7Ibs |
3351.1Ibs / 4708Ibs |
5070.6Ibs |
5342.9Ibs |
5310Ibs |
|
Dimensions (W × D × H) |
600 x1200 x2300mm |
800 x2000x2000mm |
900 x1450 x2100mm / 1200*1800*2100mm |
1200 x2000 x2000mm |
1200 x2000 x2300mm |
1651 x1061 x2242mm |