In-Row Liquid-to-Liquid CDU

The In-Row liquid-to-liquid CDU integrates control, pump power, buffering, and heat exchange functions into a single unit. Through a circulation pump, the coolant with constant pressure and flow rate is continuously delivered to the supply-side pipeline and evenly distributed to server cabinets via the looped piping network.
Contact Us

Details

The In-Row liquid-to-liquid CDU integrates control, pump power, buffering, and heat exchange functions into a single unit. Through a circulation pump, the coolant with constant pressure and flow rate is continuously delivered to the supply-side pipeline and evenly distributed to server cabinets via the looped piping network. After absorbing heat from server nodes, the cooling medium flows back through the return-side pipeline and exchanges heat with the primary-side coolant through the CDU heat exchange module. The heat is then transferred to the external environment. The cooled medium returns to the circulation pump, is pressurized, and re-enters the supply-side loop, forming a closed-loop cooling system.

 

PRODUCT FEATURES:

◆ Cooling capacity range: 300–2300 kW, suitable for large-scale data center.
◆ Redundant safety design for key components, supporting online maintenance.
◆ N+1 redundancy for pumps, control sensors, and secondary-side filters.
◆ Dual power inputs, optional ATS support.
◆ Three control modes: differential pressure, constant flow, and constant temperature.
◆ SUS304 stainless steel piping, high reliability and  coolant compatibility.
◆ Compatible with both top and bottom piping on primary and secondary sides.
◆ Integrated real-time water quality monitoring (pH, conductivity, turbidity)
◆ 7’’ LCD touch screen with PLC controller and integrated monitoring of temperature, flow, pressure, leakage, and liquid level.
◆ Supports Modbus RTU, Modbus TCP/IP, and SNMP protocols.
◆ Three-level alarm mechanism for rapid fault diagnosis.

 

BEEHE IN RACK L2L CDU TECHNICAL PARAMETERS:

Model

IB300

IB600

IB1350/IB1350P

IB1800

IB2300

Rated Cooling Capacity

300kW

600kW

1350kW

1800kW

2300kW

Coolant Type

PG25

PG25

PG25

PG25

PG25

Approach Temperature

5℃

5℃

4℃

4℃

4℃

Primary In/Out Temp

35℃/46℃

35℃/43.2℃

35℃/47.5℃

35℃/45.2℃

35℃/45.2℃

Secondary Supply/Return Temp

40℃/51℃

40℃/50.1℃

39℃/53℃

39℃/50.3℃

39℃/50.3℃

Rated Flow (Secondary)

445LPM

900LPM

1440LPM/1800LPM

2400LPM

3450LPM

Flow Range

10-100%

10-100%

10-100%

10-100%

30-100%

Available Head

21.7PSI

36PSI

36PSI

42PSI

42PSI

Input Power

3P AC380V 50/60Hz

3P AC480V 60Hz

3P AC380V 50/60Hz

3P AC480V 60Hz

3P AC380V 50/60Hz

3P AC480V 60Hz

3P AC380V50/60Hz

3P AC480V 60Hz

3P AC380V50/60Hz

3P AC480V 60Hz

Max. Power Consumption

≤5.5kW

≤12.2kW

≤19kW / ≤25kW

≤32.8kW

≤40kW

ATS

Yes

Yes

Yes

Yes

Yes

Pump Configuration

1+1

1+1

1+1

1+1

1+1

Secondary Filter

100μm

50μm

50μm

50μm

25μm

Primary  Filter

500μm

500μm

500μm

500μm

500μm

Communication Protocols

Modbus RTU&TCP/IP&SNMP

Modbus RTU&TCP/IP&SNMP

Modbus RTU&TCP/IP&SNMP 

Modbus RTU&TCP/IP&SNMP

Modbus RTU&TCP/IP&SNMP

Group Control

Yes

Yes

Yes

Yes

Yes

Water Quality Monitoring

Yes

Yes

Yes

Yes

Yes

Auto Refill Function

Yes

Yes

Yes

Yes

Yes

Net Weight

1297Ibs

1763.7Ibs

3351.1Ibs / 4708Ibs

5070.6Ibs

5342.9Ibs

Dimensions (W x D x H)

600 x1200 x2300mm

800 x2000x2000mm

900 x1450 x2100mm /1200*1800*2100mm

1200 x2000 x2000mm

1200 x2000 x2300mm